PITAGORA 5700

ENVIRONMENTAL MONITORING SYSTEM

The PITAGORA 5700 environmental monitoring system is a modular and flexible system, consisting of wall mountable equipment, specifically designed to detect area and air radioactivity. The system allows both dose-rate monitoring of gamma/neutron fields (Area monitoring) and activity measurements of air contamination (Air and/or Stack monitoring).

The basic structure of the PITAGORA 5700 is composed of up to 45 local units (detector + SATURN ratemeter) and a central unit (CPC computer + 5700 sMON software + Junction Box).

The recommended distance between detectors and the connected ratemeter is about 15-30 m. The system supports also the NAUSICAA 5301 IC series, the gamma-neutron monitoring station SATURN 5702, and Pulsed Field monitoring equipment.

The system’s central unit collects the data of all the local units of the PITAGORA 5700. The connected units may be the local ratemeters (area and stack monitoring) and the APU control unit of the MISTRAL XM air monitor. The local units are connected to the central unit via Ethernet cables, or RS485 for distances > 100 m.

All main monitoring functions are available to the User both locally and remotely at the central unit. The supplied 5700 sMON software provides data acquisition, processing, displaying, and storage. Furthermore, it allows setting operational parameters, verifies alarm thresholds, produces reports, and recalls historical data.

The PITAGORA 5700 system may be configured on the basis the following components:

  • PITAGORA CENTRAL UNIT control station including:
    • Power supply and Ethernet/RS485 network unit (Junction Box with switch)
    • CPC Data concentrator PC
    • 5700 sMON Software
    • Up to 45 local units: area monitors, air monitors and/or stack monitors
  • Area dose monitors, composed by:
    • SATURN ratemeter (local acquisition and control unit)
    • Gamma or Neutron detector (NAUSICAA 5301 IC and SATURN 5702 don’t need the external ratemeter)
    • ALU alarm unit (optional)
  • Stack monitors, composed by:
    • SATURN ratemeter (local acquisition and control unit)
    • PNAI 2″x2″ NaI(Tl) scintillation detector
    • PNAI-ATH Air-tight enclosure
    • SDU-1M Off-line mounting set for high-sensitivity stack monitoring (optional)
    • ALU alarm unit (optional)
    • STACK-DFM Flowmeter for released activity calculation (optional)
  • MISTRAL XM Stack monitor, composed by:
    • APU Local acquisition and control unit for multichannel stack monitoring
    • PNAI-MC 2″ x 2″ NaI(Tl) scintillation detector and multichannel electronics
    • SDU-XM Off-line mounting set for high-sensitivity stack monitoring
    • 1 ALU alarm unit (optional)
    • STACK-DFM Flowmeter for released activity calculation (optional)
  • Connection cables

5700 sMON SOFTWARE

The 5700 sMON software main features are:

  • Continuous data acquisition from the local monitors
  • Real time display on a synoptic screen of acquired data, alarm and working status
  • Alarm threshold setting
  • Visual and acoustic warning in case of alarms and errors
  • Average data computed on 3 different time bases
  • Measurement and status storage on hard disk
  • Graphic display and print of archived data
  • Real time and stored data display from a remote station connected through local network

 

Central processing unit Options   Control unit
(up to 45)
Detector
(1x unit)
Options
PITAGORA CENTRAL UNIT (CPC + Junction Box) PRINTER Area dose
monitor
SATURN series GM-1
PCP
GMP-WR
ICP
LUPIN 5401
ALU

SSD Calibration

NAUSICAA 5301 IC series and SATURN 5702 (no external ratemeter needed)
Stack monitor
On-line
SATURN series PNAI ALU

STACK-DFM

Stack monitor
Off-line
SATURN series PNAI
+ SDU-1M
ALU

STACK-DFM

Air/Stack monitor
MISTRAL XM
APU PNAI-MC
+ SDU-XM
ALU

STACK-DFM

Highlights